ACCA Manual D • 0.1 in. wg Friction1000 CFM • 2.5 TonsWhisper Quiet (<700 FPM)

1,000 CFM Duct Size: 2.5 Ton HVAC Main Trunk Line

Calculated duct sizing specifications for 1000 CFM of conditioned airflow. Sized via the Equal Friction Method and Huebscher equivalent rectangular equation to maintain static pressure and eliminate air rush noise.

Recalculate in Custom Duct Tool
Round Duct Size14" RoundSpiral / Snaplock Pipe
Air Velocity935 FPMFeet Per Minute
Cooling Tonnage2.5 Tons@ 400 CFM / Ton
Register / Grille10x22Face Dimension

Equivalent Rectangular Duct Sizing Schedule

Exact rectangular sheet metal dimensions offering equivalent airflow resistance to a 14" round pipe

De = 1.30 × (ab)^0.625 / (a+b)^0.25
Height (Depth)WidthCross AreaAir VelocityAspect RatioSMACNA Status
8" Deep26" Wide208 sq in692 FPM3.3:1Acceptable (<3:1)
10" Deep20" Wide200 sq in720 FPM2.0:1Optimal (<2:1)
12" Deep18" Wide216 sq in667 FPM1.5:1Optimal (<2:1)

Air Terminal & Grille Sizing Guidelines

Recommended face velocities to prevent whistling diffuser vanes

Supply Register Specifications
Recommended Grille Size:10x22 Supply Trunk / 20x20 Return Grille
Maximum Target Velocity:500–700 FPM at register face
Diffuser Throw:Spread toward outside walls
Return Air Intake Rules
Return Velocity Target:<450 FPM through filter face
Filter Surface Requirement:Minimum 2 sq ft per Ton
Return Friction Target:0.05 – 0.08 in. wg / 100 ft

HVAC Sheet Metal & Installation Directives

  • A 14-inch round metal duct or 10x20 rectangular duct is the industry benchmark for 2.5 tons (1,000 CFM).
  • Maintain an aspect ratio under 3:1 on rectangular ductwork to prevent excessive friction loss and turbulence.

Frequently Asked Duct Sizing Questions

What size duct is required for 1,000 CFM?

A 14-inch round duct or a 10x20 rectangular sheet metal trunk is recommended for 1,000 CFM.

Related Airflow Sizing Schedules

View All 25 Schedules →