NEC 310.16 Code StandardOne-Way Circuit: 200 Feet120 Volts AC

Wire Size for 15 Amp Circuit at 200 Feet

Official National Electrical Code (NEC) sizing recommendation for a 15 Amp breaker over a 200-foot one-way conduit run on a 120V supply circuit.

Recommended Copper Conductor (Cu)
#6 AWGUpsized for <3% drop
Voltage Drop: 15.35% (Base size without drop: #14 AWG)
Recommended Aluminum Conductor (Al)
#4 AWGUpsized for <3% drop
Aluminum not permitted for 15A branch circuits

Full Installation & Conduit Specifications

Interactive Calculator
Overcurrent Protection15A 1-Pole (120V)Standard Breaker Trip
Max Continuous Load12 Amperes80% NEC Continuous Rule
Conduit Sizing3/4" EMT or Schedule 40 PVCMax 40% fill limit
Circuit Distance200 Feet (One-Way)61m total span

Voltage Drop Alert: Base #14 AWG Wire Exceeds 3% (15.35%)

NEC Section 210.19(A) Informational Note 4 recommends that feeder and branch circuits maintain voltage drop under 3% (and 5% total) to protect appliances from motor burnout and voltage sagging. Using upsized #6 AWG copper wire successfully brings voltage drop back under safe limits.

Common Real-World Applications for this Circuit:
✓ Standard Bedroom/Living Room Receptacles✓ LED Lighting Circuits✓ Smoke Detector Loops

Frequently Asked Technical Questions

What size copper wire is required for a 15 amp breaker at 200 feet?

Due to voltage drop over 200 feet (15.35% on base wire), the National Electrical Code (NEC) recommends upsizing copper wire from #14 AWG to #6 AWG. This keeps the voltage drop under 3%, protecting your equipment from overheating and brownout damage.

Can I use aluminum wire for 15 amps at 200 feet?

No. The NEC does not permit aluminum wiring on standard 15-amp branch circuits. You must use copper (#14 AWG or upsized).

What is the maximum continuous load permitted on a 15 amp breaker?

Per NEC Article 210.20, continuous loads (operating for 3 hours or longer, such as EV chargers or heaters) cannot exceed 80% of the breaker rating. For a 15A breaker, your maximum continuous draw is 12.0 Amps.

What size conduit is recommended for this 200 ft run?

Based on Chapter 9, Tables 1 and 4 of the NEC for up to 3-4 current-carrying conductors plus ground at a 40% maximum conduit fill, we recommend using 3/4" EMT or Schedule 40 PVC.

Related Electrical Distance & Amperage Runs

View All 72 Combinations