NEC 310.16 Code StandardOne-Way Circuit: 250 Feet120 Volts AC

Wire Size for 20 Amp Circuit at 250 Feet

Official National Electrical Code (NEC) sizing recommendation for a 20 Amp breaker over a 250-foot one-way conduit run on a 120V supply circuit.

Recommended Copper Conductor (Cu)
#4 AWGUpsized for <3% drop
Voltage Drop: 16.08% (Base size without drop: #12 AWG)
Recommended Aluminum Conductor (Al)
#2 AWGUpsized for <3% drop
Voltage Drop: 16.67% (Base size: #10 AWG)

Full Installation & Conduit Specifications

Interactive Calculator
Overcurrent Protection20A 1-Pole (120V)Standard Breaker Trip
Max Continuous Load16 Amperes80% NEC Continuous Rule
Conduit Sizing1" EMT or Schedule 40 PVCMax 40% fill limit
Circuit Distance250 Feet (One-Way)76m total span

Voltage Drop Alert: Base #12 AWG Wire Exceeds 3% (16.08%)

NEC Section 210.19(A) Informational Note 4 recommends that feeder and branch circuits maintain voltage drop under 3% (and 5% total) to protect appliances from motor burnout and voltage sagging. Using upsized #4 AWG copper wire successfully brings voltage drop back under safe limits.

Common Real-World Applications for this Circuit:
✓ Kitchen Small Appliance Branch Circuits✓ Bathroom GFCI Outlets✓ Garage Workbenches

Frequently Asked Technical Questions

What size copper wire is required for a 20 amp breaker at 250 feet?

Due to voltage drop over 250 feet (16.08% on base wire), the National Electrical Code (NEC) recommends upsizing copper wire from #12 AWG to #4 AWG. This keeps the voltage drop under 3%, protecting your equipment from overheating and brownout damage.

Can I use aluminum wire for 20 amps at 250 feet?

Yes, you can use aluminum or copper-clad aluminum wiring. For 20A at 250ft, you will need #2 AWG aluminum conductors with terminals rated AL7CU or AL9CU and anti-oxidant paste where required.

What is the maximum continuous load permitted on a 20 amp breaker?

Per NEC Article 210.20, continuous loads (operating for 3 hours or longer, such as EV chargers or heaters) cannot exceed 80% of the breaker rating. For a 20A breaker, your maximum continuous draw is 16.0 Amps.

What size conduit is recommended for this 250 ft run?

Based on Chapter 9, Tables 1 and 4 of the NEC for up to 3-4 current-carrying conductors plus ground at a 40% maximum conduit fill, we recommend using 1" EMT or Schedule 40 PVC.