NEC 310.16 Code StandardOne-Way Circuit: 300 Feet240 Volts AC

Wire Size for 200 Amp Circuit at 300 Feet

Official National Electrical Code (NEC) sizing recommendation for a 200 Amp breaker over a 300-foot one-way conduit run on a 240V supply circuit.

Recommended Copper Conductor (Cu)
250 kcmilUpsized for <3% drop
Voltage Drop: 3.83% (Base size without drop: 3/0 AWG)
Recommended Aluminum Conductor (Al)
250 kcmil
Voltage Drop: 4.23% (Base size: 250 kcmil)

Full Installation & Conduit Specifications

Interactive Calculator
Overcurrent Protection200A 2-Pole (240V)Standard Breaker Trip
Max Continuous Load160 Amperes80% NEC Continuous Rule
Conduit Sizing2" or 2-1/2" EMT / Schedule 80 PVCMax 40% fill limit
Circuit Distance300 Feet (One-Way)91m total span

Voltage Drop Alert: Base 3/0 AWG Wire Exceeds 3% (3.83%)

NEC Section 210.19(A) Informational Note 4 recommends that feeder and branch circuits maintain voltage drop under 3% (and 5% total) to protect appliances from motor burnout and voltage sagging. Using upsized 250 kcmil copper wire successfully brings voltage drop back under safe limits.

Common Real-World Applications for this Circuit:
✓ Main Electrical Service Entrance (200A Panel)✓ Full-House Service Drop Feeder✓ Large Commercial Subpanel

Frequently Asked Technical Questions

What size copper wire is required for a 200 amp breaker at 300 feet?

Due to voltage drop over 300 feet (3.83% on base wire), the National Electrical Code (NEC) recommends upsizing copper wire from 3/0 AWG to 250 kcmil. This keeps the voltage drop under 3%, protecting your equipment from overheating and brownout damage.

Can I use aluminum wire for 200 amps at 300 feet?

Yes, you can use aluminum or copper-clad aluminum wiring. For 200A at 300ft, you will need 250 kcmil aluminum conductors with terminals rated AL7CU or AL9CU and anti-oxidant paste where required.

What is the maximum continuous load permitted on a 200 amp breaker?

Per NEC Article 210.20, continuous loads (operating for 3 hours or longer, such as EV chargers or heaters) cannot exceed 80% of the breaker rating. For a 200A breaker, your maximum continuous draw is 160.0 Amps.

What size conduit is recommended for this 300 ft run?

Based on Chapter 9, Tables 1 and 4 of the NEC for up to 3-4 current-carrying conductors plus ground at a 40% maximum conduit fill, we recommend using 2" or 2-1/2" EMT / Schedule 80 PVC.