NEC 310.16 Code StandardOne-Way Circuit: 100 Feet240 Volts AC

Wire Size for 30 Amp Circuit at 100 Feet

Official National Electrical Code (NEC) sizing recommendation for a 30 Amp breaker over a 100-foot one-way conduit run on a 240V supply circuit.

Recommended Copper Conductor (Cu)
#8 AWGUpsized for <3% drop
Voltage Drop: 3.02% (Base size without drop: #10 AWG)
Recommended Aluminum Conductor (Al)
#6 AWGUpsized for <3% drop
Voltage Drop: 3.15% (Base size: #8 AWG)

Full Installation & Conduit Specifications

Interactive Calculator
Overcurrent Protection30A 2-Pole (240V)Standard Breaker Trip
Max Continuous Load24 Amperes80% NEC Continuous Rule
Conduit Sizing3/4" EMT or Schedule 40 PVCMax 40% fill limit
Circuit Distance100 Feet (One-Way)30m total span

Voltage Drop Alert: Base #10 AWG Wire Exceeds 3% (3.02%)

NEC Section 210.19(A) Informational Note 4 recommends that feeder and branch circuits maintain voltage drop under 3% (and 5% total) to protect appliances from motor burnout and voltage sagging. Using upsized #8 AWG copper wire successfully brings voltage drop back under safe limits.

Common Real-World Applications for this Circuit:
✓ Electric Clothes Dryers✓ Residential Water Heaters✓ Central A/C Condensers (2-3 Ton)

Frequently Asked Technical Questions

What size copper wire is required for a 30 amp breaker at 100 feet?

Due to voltage drop over 100 feet (3.02% on base wire), the National Electrical Code (NEC) recommends upsizing copper wire from #10 AWG to #8 AWG. This keeps the voltage drop under 3%, protecting your equipment from overheating and brownout damage.

Can I use aluminum wire for 30 amps at 100 feet?

Yes, you can use aluminum or copper-clad aluminum wiring. For 30A at 100ft, you will need #6 AWG aluminum conductors with terminals rated AL7CU or AL9CU and anti-oxidant paste where required.

What is the maximum continuous load permitted on a 30 amp breaker?

Per NEC Article 210.20, continuous loads (operating for 3 hours or longer, such as EV chargers or heaters) cannot exceed 80% of the breaker rating. For a 30A breaker, your maximum continuous draw is 24.0 Amps.

What size conduit is recommended for this 100 ft run?

Based on Chapter 9, Tables 1 and 4 of the NEC for up to 3-4 current-carrying conductors plus ground at a 40% maximum conduit fill, we recommend using 3/4" EMT or Schedule 40 PVC.