ACCA Manual D • 0.08 in. wg Friction150 CFM • 0.375 TonsStandard Residential (<900 FPM)

150 CFM Duct Size: Master Bedroom & Large Suite Branch

Calculated duct sizing specifications for 150 CFM of conditioned airflow. Sized via the Equal Friction Method and Huebscher equivalent rectangular equation to maintain static pressure and eliminate air rush noise.

Recalculate in Custom Duct Tool
Round Duct Size6" RoundSpiral / Snaplock Pipe
Air Velocity764 FPMFeet Per Minute
Cooling Tonnage0.375 Tons@ 400 CFM / Ton
Register / Grille4x12Face Dimension

Equivalent Rectangular Duct Sizing Schedule

Exact rectangular sheet metal dimensions offering equivalent airflow resistance to a 6" round pipe

De = 1.30 × (ab)^0.625 / (a+b)^0.25
Height (Depth)WidthCross AreaAir VelocityAspect RatioSMACNA Status
6" Deep8" Wide48 sq in450 FPM1.3:1Optimal (<2:1)
4" Deep12" Wide48 sq in450 FPM3.0:1Acceptable (<3:1)

Air Terminal & Grille Sizing Guidelines

Recommended face velocities to prevent whistling diffuser vanes

Supply Register Specifications
Recommended Grille Size:4x12 or 6x10 Supply Register
Maximum Target Velocity:500–700 FPM at register face
Diffuser Throw:Spread toward outside walls
Return Air Intake Rules
Return Velocity Target:<450 FPM through filter face
Filter Surface Requirement:Minimum 2 sq ft per Ton
Return Friction Target:0.05 – 0.08 in. wg / 100 ft

HVAC Sheet Metal & Installation Directives

  • A 6-inch rigid metal duct handles 150 CFM at 764 FPM. For flex duct, upsize to 7-inch to avoid velocity whistle.
  • Use a 4x12 register boot with a curved-blade diffuser to ensure throw covers the outside wall and windows.

Frequently Asked Duct Sizing Questions

Can a 6-inch flex duct handle 150 CFM?

A 6-inch flex duct will be noisy and cause static pressure restriction at 150 CFM (velocity over 850 FPM). A 7-inch or 8-inch flex duct is recommended for 150 CFM.