ACCA Manual D • 0.08 in. wg Friction250 CFM • 0.625 TonsWhisper Quiet (<700 FPM)

250 CFM Duct Size: Kitchen & Family Room Open Area

Calculated duct sizing specifications for 250 CFM of conditioned airflow. Sized via the Equal Friction Method and Huebscher equivalent rectangular equation to maintain static pressure and eliminate air rush noise.

Recalculate in Custom Duct Tool
Round Duct Size8" RoundSpiral / Snaplock Pipe
Air Velocity716 FPMFeet Per Minute
Cooling Tonnage0.625 Tons@ 400 CFM / Ton
Register / Grille6x14Face Dimension

Equivalent Rectangular Duct Sizing Schedule

Exact rectangular sheet metal dimensions offering equivalent airflow resistance to a 8" round pipe

De = 1.30 × (ab)^0.625 / (a+b)^0.25
Height (Depth)WidthCross AreaAir VelocityAspect RatioSMACNA Status
6" Deep12" Wide72 sq in500 FPM2.0:1Optimal (<2:1)
8" Deep10" Wide80 sq in450 FPM1.3:1Optimal (<2:1)

Air Terminal & Grille Sizing Guidelines

Recommended face velocities to prevent whistling diffuser vanes

Supply Register Specifications
Recommended Grille Size:6x14 or 8x12 Register
Maximum Target Velocity:500–700 FPM at register face
Diffuser Throw:Spread toward outside walls
Return Air Intake Rules
Return Velocity Target:<450 FPM through filter face
Filter Surface Requirement:Minimum 2 sq ft per Ton
Return Friction Target:0.05 – 0.08 in. wg / 100 ft

HVAC Sheet Metal & Installation Directives

  • An 8-inch round duct is the standard size for 250 CFM, keeping velocity well below 750 FPM.
  • In kitchens, locate supply registers away from gas cooktops and exhaust hoods to prevent disturbing burner flames.

Frequently Asked Duct Sizing Questions

How much CFM can an 8-inch duct handle?

An 8-inch round metal duct comfortably delivers 200 to 260 CFM at standard residential friction rates (0.08 to 0.10 in. wg).

Related Airflow Sizing Schedules

View All 25 Schedules →