ACCA Manual D • 0.08 in. wg Friction350 CFM • 0.875 TonsWhisper Quiet (<700 FPM)

350 CFM Duct Size: Bonus Room & Finished Attic Branch

Calculated duct sizing specifications for 350 CFM of conditioned airflow. Sized via the Equal Friction Method and Huebscher equivalent rectangular equation to maintain static pressure and eliminate air rush noise.

Recalculate in Custom Duct Tool
Round Duct Size9" RoundSpiral / Snaplock Pipe
Air Velocity792 FPMFeet Per Minute
Cooling Tonnage0.875 Tons@ 400 CFM / Ton
Register / Grille8x14Face Dimension

Equivalent Rectangular Duct Sizing Schedule

Exact rectangular sheet metal dimensions offering equivalent airflow resistance to a 9" round pipe

De = 1.30 × (ab)^0.625 / (a+b)^0.25
Height (Depth)WidthCross AreaAir VelocityAspect RatioSMACNA Status
8" Deep14" Wide112 sq in450 FPM1.8:1Optimal (<2:1)
6" Deep18" Wide108 sq in467 FPM3.0:1Acceptable (<3:1)

Air Terminal & Grille Sizing Guidelines

Recommended face velocities to prevent whistling diffuser vanes

Supply Register Specifications
Recommended Grille Size:8x14 or Dual 6x12 Registers
Maximum Target Velocity:500–700 FPM at register face
Diffuser Throw:Spread toward outside walls
Return Air Intake Rules
Return Velocity Target:<450 FPM through filter face
Filter Surface Requirement:Minimum 2 sq ft per Ton
Return Friction Target:0.05 – 0.08 in. wg / 100 ft

HVAC Sheet Metal & Installation Directives

  • A 9-inch round duct (or 10-inch flex duct) provides excellent airflow with low static pressure resistance.
  • Insulate attic ductwork to minimum R-8 with sealed mastic joints per IECC requirements.

Frequently Asked Duct Sizing Questions

What size duct is required for 350 CFM?

A 9-inch round metal duct or an 8x14 rectangular trunk is optimal for 350 CFM.

Related Airflow Sizing Schedules

View All 25 Schedules →