NEC 310.16 Code StandardOne-Way Circuit: 100 Feet240 Volts AC

Wire Size for 100 Amp Circuit at 100 Feet

Official National Electrical Code (NEC) sizing recommendation for a 100 Amp breaker over a 100-foot one-way conduit run on a 240V supply circuit.

Recommended Copper Conductor (Cu)
#3 AWG
Voltage Drop: 2.04% (Base size without drop: #3 AWG)
Recommended Aluminum Conductor (Al)
#1 AWG
Voltage Drop: 2.11% (Base size: #1 AWG)

Full Installation & Conduit Specifications

Interactive Calculator
Overcurrent Protection100A 2-Pole (240V)Standard Breaker Trip
Max Continuous Load80 Amperes80% NEC Continuous Rule
Conduit Sizing1" EMT or Schedule 40 PVCMax 40% fill limit
Circuit Distance100 Feet (One-Way)30m total span

Code Compliant: Voltage Drop is Within Safe Tolerance (2.04%)

At 100 feet under a 100A load, standard #3 AWG copper conductors experience only a 2.04% voltage reduction. No wire gauge upsizing is required.

Common Real-World Applications for this Circuit:
✓ 100-Amp Subpanel (Detached Barn/ADU)✓ All-Electric Whole Home Upgrade Feeder✓ Commercial Welders

Frequently Asked Technical Questions

What size copper wire is required for a 100 amp breaker at 100 feet?

For a 100 amp circuit at 100 feet on a 240V system, standard #3 AWG copper wire is sufficient. The calculated voltage drop is only 2.04%, well within the NEC recommended 3% limit.

Can I use aluminum wire for 100 amps at 100 feet?

Yes, you can use aluminum or copper-clad aluminum wiring. For 100A at 100ft, you will need #1 AWG aluminum conductors with terminals rated AL7CU or AL9CU and anti-oxidant paste where required.

What is the maximum continuous load permitted on a 100 amp breaker?

Per NEC Article 210.20, continuous loads (operating for 3 hours or longer, such as EV chargers or heaters) cannot exceed 80% of the breaker rating. For a 100A breaker, your maximum continuous draw is 80.0 Amps.

What size conduit is recommended for this 100 ft run?

Based on Chapter 9, Tables 1 and 4 of the NEC for up to 3-4 current-carrying conductors plus ground at a 40% maximum conduit fill, we recommend using 1" EMT or Schedule 40 PVC.