NEC 310.16 Code StandardOne-Way Circuit: 250 Feet240 Volts AC

Wire Size for 100 Amp Circuit at 250 Feet

Official National Electrical Code (NEC) sizing recommendation for a 100 Amp breaker over a 250-foot one-way conduit run on a 240V supply circuit.

Recommended Copper Conductor (Cu)
1/0 AWGUpsized for <3% drop
Voltage Drop: 5.1% (Base size without drop: #3 AWG)
Recommended Aluminum Conductor (Al)
3/0 AWGUpsized for <3% drop
Voltage Drop: 5.27% (Base size: #1 AWG)

Full Installation & Conduit Specifications

Interactive Calculator
Overcurrent Protection100A 2-Pole (240V)Standard Breaker Trip
Max Continuous Load80 Amperes80% NEC Continuous Rule
Conduit Sizing1-1/4" EMT or Schedule 40 PVCMax 40% fill limit
Circuit Distance250 Feet (One-Way)76m total span

Voltage Drop Alert: Base #3 AWG Wire Exceeds 3% (5.1%)

NEC Section 210.19(A) Informational Note 4 recommends that feeder and branch circuits maintain voltage drop under 3% (and 5% total) to protect appliances from motor burnout and voltage sagging. Using upsized 1/0 AWG copper wire successfully brings voltage drop back under safe limits.

Common Real-World Applications for this Circuit:
✓ 100-Amp Subpanel (Detached Barn/ADU)✓ All-Electric Whole Home Upgrade Feeder✓ Commercial Welders

Frequently Asked Technical Questions

What size copper wire is required for a 100 amp breaker at 250 feet?

Due to voltage drop over 250 feet (5.1% on base wire), the National Electrical Code (NEC) recommends upsizing copper wire from #3 AWG to 1/0 AWG. This keeps the voltage drop under 3%, protecting your equipment from overheating and brownout damage.

Can I use aluminum wire for 100 amps at 250 feet?

Yes, you can use aluminum or copper-clad aluminum wiring. For 100A at 250ft, you will need 3/0 AWG aluminum conductors with terminals rated AL7CU or AL9CU and anti-oxidant paste where required.

What is the maximum continuous load permitted on a 100 amp breaker?

Per NEC Article 210.20, continuous loads (operating for 3 hours or longer, such as EV chargers or heaters) cannot exceed 80% of the breaker rating. For a 100A breaker, your maximum continuous draw is 80.0 Amps.

What size conduit is recommended for this 250 ft run?

Based on Chapter 9, Tables 1 and 4 of the NEC for up to 3-4 current-carrying conductors plus ground at a 40% maximum conduit fill, we recommend using 1-1/4" EMT or Schedule 40 PVC.